fire code, O. Reg. 213/07

Section 5.3.1.2

Cite as fire code, O. Reg. 213/07, s. 5.3.1.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Building and machinery surfaces shall be kept clean of accumulations of combustible dusts using cleaning equipment that (a) is made of materials that will not create electrostatic charges or sparks, (b) is electrically conductive and bonded to ground, and (c) except as permitted in Sentence (3), removes the dust to a safe location by vacuum. (2) Cleaning equipment required in Sentence (1) that is used in an atmosphere containing combustible dusts shall conform to the Electrical Safety Code made under the Electricity Act, 1998. (3) Where it is not possible to effectively remove the dust by vacuum, it is permitted to use compressed air or other means that will cause the dust to become suspended in the air during removal if, in the dust removal area, (a) all sources of ignition are eliminated, and (b) all machinery and equipment is de-energized, unless such machinery or equipment is suitable for use in atmospheres containing combustible dusts, in conformance with the Electrical Safety Code made under the Electricity Act, 1998. Dust-collecting systems
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.