fire code, O. Reg. 213/07
Section 5.3.1.12
Cite as fire code, O. Reg. 213/07, s. 5.3.1.12 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Permanently open vent stacks may be used to ventilate storage containers where mechanical dust-collecting systems are not practical, provided that the vent stacks
(a) have a cross-sectional area not less than twice that of spouts discharging into the container,
(b) are installed not more than 30 degrees from the vertical,
(c) extend from the top of the container to a point not less than 1.2 m above the roof, and
(d) are designed to prevent the entry of snow and rain.
Subsection 5.3.2. Woodworking Operations
Exhaust systems
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.