(1) Hot work shall not be performed on containers, equipment, or piping containing flammable liquids, combustible liquids or flammable gases unless (a) they have been cleaned and tested with a listed gas detector, such as one conforming to CSA C22.2 No. 152, “Combustible Gas Detection Instruments”, to ascertain that they are free of explosive vapours, or (b) safety measures are taken in conformance with good engineering practice. (2) Hot work operations shall not be undertaken on a totally enclosed container. (3) At least one portable extinguisher conforming to Section 6.2 shall be provided in the hot work area. SECTION 5.18 INDUSTRIAL OVENS FOR BAKING AND DRYING PROCESSES Subsection 5.18.1. Application Application