fire code, O. Reg. 213/07

Section 5.17.3.1

Cite as fire code, O. Reg. 213/07, s. 5.17.3.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Hot work operations in buildings shall be carried out in areas that (a) are free of combustible and flammable contents, and (b) have walls, ceilings and floors of noncombustible construction or that are lined with noncombustible materials. (2) When it is not practical to undertake hot work operations in areas described in Sentence (1), combustible and flammable materials shall either be kept at least 15 m from the work area or otherwise protected against ignition by sheet metal or other noncombustible material. (3) Any process or activity that produces flammable gases or vapours, combustible dusts or combustible fibres in quantities sufficient to create a fire or explosion hazard shall be interrupted and the hazardous conditions shall be removed before any hot work is carried out. Work adjacent to piping