fire code, O. Reg. 213/07

Section 5.13.6.2

Cite as fire code, O. Reg. 213/07, s. 5.13.6.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Dip tanks with over 550 L capacity or with over 1 m2 liquid surface area shall be protected by (a) a cover actuated by a device that (i) automatically closes the cover in the event of a fire, and (ii) permits manual operation of the cover, or (b) an approved automatic extinguishing system of a water spray, foam, carbon dioxide or dry chemical type. Flammable liquids or combustible liquids
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.