fire code, O. Reg. 213/07

Section 5.12.4.5

Cite as fire code, O. Reg. 213/07, s. 5.12.4.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except for water-wash filtration systems, the exhaust outlet to atmosphere from spray booths and spray rooms shall (a) be 1.8 m from any combustible exterior wall or roof, and (b) be located so that the air does not discharge toward any combustible surface or unprotected opening within 7.5 m. Subsection 5.12.5. Electrical Equipment Electrical equipment
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.