fire code, O. Reg. 213/07

Section 5.12.4.3

Cite as fire code, O. Reg. 213/07, s. 5.12.4.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Where exhaust ducts pass through combustible roofs or partitions, metal collars shall provide not less than a 100 mm clearance between the duct and combustible material. (2) The space between the duct and combustible material shall be sealed with noncombustible insulating material. Access doors