fire code, O. Reg. 213/07

Section 5.12.3.1

Cite as fire code, O. Reg. 213/07, s. 5.12.3.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Ventilation shall be provided in all spraying areas to maintain (a) the concentration of flammable vapours at or below 25% of their lower explosive limit, and (b) the concentration of combustible dusts at or below 50% of their minimum explosible concentration or 15g/m3 when the minimum explosible concentration cannot be established. Exhaust for spray booths
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.