fire code, O. Reg. 213/07
Section 5.12.2.1
Cite as fire code, O. Reg. 213/07, s. 5.12.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Spray booths and spray rooms shall have walls and ceilings that consist of steel frames covered with sheet steel having a minimum thickness of 1.14 mm or be of equivalent noncombustible construction.
(2) Walls and ceilings of spray rooms that are susceptible to paint residue accumulations and interior surfaces of spray booths shall be smooth and continuous.
(3) Floors of spray booths and spray rooms and the operator’s working area shall be of noncombustible materials.
Baffle plates
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.