fire code, O. Reg. 213/07

Section 5.11.2.5

Cite as fire code, O. Reg. 213/07, s. 5.11.2.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) A firewatch shall be provided whenever an open flame torch or other ignition source is used for hot surface applications in or on a building and shall include (a) any area where combustible materials used in building construction or contents are located within 5 m of persons using an open flame torch or other ignition source, (b) any area of the building exposed as a result of unprotected roof or wall openings located within 5 m of persons using an open flame torch or other ignition source, and (c) any area where combustibles on the underside of roofs or the opposite side of walls might be ignited as a result of persons using an open flame torch or other ignition source. (2) If a firewatch is required, the areas shall be toured by firewatch personnel at least once each hour. (3) Facilities shall be provided to enable the firewatch personnel to (a) ensure that a fire warning is sounded to notify occupants, and (b) communicate with the fire department. (4) The firewatch personnel shall be equipped with portable illumination and protective equipment. (5) A firewatch shall be conducted from the beginning of a hot surface application until (a) at least 3 hours after the application ceases, or (b) at least 2 hours after the application ceases if a hand-held thermal imaging camera is used to assist in detecting hidden hot spots. Portable extinguishers
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.