fire code, O. Reg. 213/07

Section 5.11.2.3

Cite as fire code, O. Reg. 213/07, s. 5.11.2.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Bitumen kettles shall (a) not be located in a building or on a roof of a building, (b) not be located in a fire access route, (c) not be located within 3 m of a building exit or means of egress, (d) be provided with metal lids that are close-fitting and constructed of steel having a thickness of not less than No. 14 sheet metal gauge (2 mm), (e) be maintained free of excessive residue, and (f) when in operation (i) be level, with most of the weight off the tires and legs, (ii) not be heated above 260ºC, (iii) be kept clear of combustible debris or materials, and (iv) be under constant supervision by a person who is knowledgeable of operations and hazards and trained in the use of portable extinguishers. (2) Despite Sentence (1), bitumen kettles may be located on concrete roofs if roof openings within 15 m are diked to prevent spilled asphalt run-off.