fire code, O. Reg. 213/07
Section 4.9.4.3
Cite as fire code, O. Reg. 213/07, s. 4.9.4.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) An evaluation of the fire and explosion risks shall be undertaken to consider the material properties, quantities, operating conditions, storage arrangement, transportation, process design, operating and maintenance procedures.
(2) The evaluation in Sentence (1) shall result in the identification of measures that will minimize fires and explosions from occurring and mitigate the effects of a fire or explosion should it occur.
(3) Measures identified in Sentence (2) shall be implemented in conformance with good engineering practices to prevent fires and explosions from occurring.
(4) Measures identified in Sentence (2) may include but are not limited to
(a) fire detection and alarm,
(b) special fire suppression systems conforming to the standards identified in Sentences 2.1.3.5.(3) and (4),
(c) sprinkler system conforming to NFPA 13, “Standard for Installation of Sprinkler Systems”,
(d) a reliable water supply with pressure and flow rates capable of meeting the fire demands,
(e) standpipe and hose systems connected to a reliable water supply located such that vessels, pumps and other equipment containing flammable liquids or combustible liquids can be reached with at least one hose stream,
(f) combination nozzles capable of discharging a straight steam, water spray or fog,
(g) hydrants or monitor nozzles installed in accordance with NFPA 24, “Standard for the Installation of Private Fire Service Mains and their Appurtenances”,
(h) fire-proofing to protect essential equipment and controls,
(i) methods to effect an emergency shutdown of systems, and
(j) methods to protect equipment and structures from fire exposure.
(5) The evaluation and measures shall be put in writing and kept in the building for review by the Chief Fire Official.
Emergency procedures
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.