fire code, O. Reg. 213/07
Section 4.9.3.4
Cite as fire code, O. Reg. 213/07, s. 4.9.3.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
Equipment used in a building and the ventilation of the building shall be designed so as to limit flammable vapour-air mixtures under normal operating conditions to the interior of equipment and to not more than 1.5 m from such equipment.
Subsection 4.9.4. Fire Prevention and Protection
Spill and vapour control
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.