fire code, O. Reg. 213/07

Section 4.9.2.1

Cite as fire code, O. Reg. 213/07, s. 4.9.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) The location of outdoor processing equipment in process plants shall be based on its flammable liquid or combustible liquid capacity as described in Sentences (2) to (4). (2) Except as provided in Sentence (4), outdoor processing equipment having emergency relief venting and a working pressure of not more than 17 kPa (gauge) shall be separated from property lines and buildings on the same property by distances (a) equal to those in Table 4.3.2.1. for stable liquids, and (b) 2.5 times those in Table 4.3.2.1. for unstable liquids. (3) Except as provided in Sentence (4), outdoor processing equipment having emergency relief venting and a working pressure more than 17 kPa (gauge) shall be separated from property lines and buildings on the same property by distances (a) 1.5 times those in Table 4.3.2.1. for stable liquids, and (b) 4 times those in Table 4.3.2.1. for unstable liquids. (4) Where protection is not provided against fires or explosions in processing equipment, the distances in Sentences (2) and (3) shall be doubled. Subsection 4.9.3. Processing Buildings Explosion venting
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.