fire code, O. Reg. 213/07
Section 4.8.9.3
Cite as fire code, O. Reg. 213/07, s. 4.8.9.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as permitted in Sentence (2), cargo pumps shall be located
(a) on shore or on piers and wharves either of noncombustible construction or of the solid-fill type, and
(b) not less than 3 m from other buildings or structures.
(2) Where it is not practicable to install cargo pumps as required in Sentence (1), they are permitted to be installed on piers and wharves of combustible construction if located in pump houses
(a) conforming to Subsection 4.8.10., and
(b) located not less than 3 m from other buildings.
Subsection 4.8.10. Pump Houses
Construction
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.