The text

(1) At a loading or unloading facility for tank vehicles or tank cars, the horizontal distance from the fill stem to an aboveground storage tank, a building or a property line shall be not less than (a) 7.5 m for Class I liquids, and (b) 4.5 m for Class II and IIIA liquids. (2) At bulk plant rail loading and unloading facilities, the minimum distance from a loading structure to a railway line shall be in conformance with the Flammable Liquids Bulk Storage Regulations, C.R.C., c1148, made under the Railway Safety Act (Canada). (3) Buildings for the shelter of persons or pumps shall be considered a part of the loading or unloading facility. Multi-purpose facilities
Read the fire code on e-Laws ↗