fire code, O. Reg. 213/07

Section 4.7.3.2

Cite as fire code, O. Reg. 213/07, s. 4.7.3.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Dispensers used by the general public to dispense flammable liquids or combustible liquids into the fuel tanks of vehicles shall not be located at a bulk plant unless separated by a fence or equivalent barrier from the area in which the bulk storage operations are conducted. (2) Where a dispenser referred to in Sentence (1) is supplied from an aboveground storage tank (a) an automatically operated valve that is designed to open only when the dispenser is being operated shall be provided at the tank outlet, and (b) an emergency valve shall be provided for the dispenser in conformance with Sentence 4.6.6.3.(1). Dispensing into metal containers or tanks
Read the fire code on e-Laws ↗