fire code, O. Reg. 213/07
Section 4.7.2.6
Cite as fire code, O. Reg. 213/07, s. 4.7.2.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) The outdoor area occupied by aboveground storage tanks, container storage, ancillary equipment and unloading facilities shall be surrounded by a firmly anchored fence that is
(a) substantially constructed to discourage climbing and unauthorized entry,
(b) not less than 1.8 m high, and
(c) provided with gates that shall be locked when the storage area is not staffed.
(2) When in a fire department access route, the gates required in Clause (1)(c) shall be of adequate width and design and in a location that readily permits the entry of fire department vehicles.
(3) Fencing that is installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continues to meet those requirements is deemed to comply with Sentence (2).
Subsection 4.7.3. Dispensing
Interconnection
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.