fire code, O. Reg. 213/07

Section 4.6.6.5

Cite as fire code, O. Reg. 213/07, s. 4.6.6.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as permitted in Sentence (2), tanks and pumps not integral with the dispenser at marine fuel-dispensing stations shall be located on the shore or on a pier of the solid-fill type. (2) Where shore locations would result in excessively long supply lines to the dispenser, storage tanks are permitted to be installed on a pier provided that (a) the applicable portions of Subsection 4.3.7. relating to spacing, secondary containment and piping are complied with, and (b) the quantity stored does not exceed 5000 L aggregate capacity. (3) No storage tank at a marine fuel-dispensing station shall be located closer than 4.5 m horizontally from the normal annual high-water mark. (4) Storage tanks located on shore and supplying marine fuel-dispensing stations are permitted to be located aboveground where rock or a high water table make underground tanks impracticable. (5) Where storage tanks at a marine fuel-dispensing station are elevated above the dispenser, an automatically operated valve that is designed to open only when the dispenser is being operated, so as to prevent gravity draining of the tank in the event of a rupture of the supply line to the dispenser, shall be provided at the storage tank outlet, positioned adjacent to and outside the valve specified in Article 4.3.6.1. (6) Piping between storage tanks located on shore and dispensers at a marine fuel-dispensing station shall conform to Section 4.5, except that where dispensing is from a floating structure, it is permitted to use suitable lengths of flexible hose designed in conformance with good engineering practice between the piping on shore and the piping on the floating structure. Subsection 4.6.7. Spill Control Spill control
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.