The text
(1) A device to shut off power to all dispensers and pumps shall be provided at a location not less than 6 m and not more than 30 m away from the dispensers and pumps.
(2) The device required in Sentence (1) shall be clearly identified and readily accessible to attendants and emergency responders.
(3) Steel shut-off valves shall be provided at connecting outlets on aboveground storage tanks.