fire code, O. Reg. 213/07
Section 4.6.2.1
Cite as fire code, O. Reg. 213/07, s. 4.6.2.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentences (2) to (5), the installation of outside aboveground storage tanks at fuel-dispensing stations shall be in conformance with Subsection 4.3.2.
(2) Except as permitted in Sentence (3), outside aboveground storage tanks at fuel-dispensing stations shall have an individual capacity of not more than 80000 L, and their aggregate capacity shall not exceed 200000 L.
(3) The individual capacity of outside aboveground storage tanks at fuel-dispensing stations is permitted to exceed the individual capacity limit of 80000 L required in Sentence (2), provided
(a) they conform to ULC-S655, “Aboveground Protected Tank Assemblies for Flammable and Combustible Liquids”, and
(b) their aggregate capacity does not exceed 200000 L.
(4) Outside aboveground storage tanks at fuel-dispensing stations shall be provided with
(a) physical protection against collision damage,
(b) measures to prevent unauthorized access to the storage tank and its ancillary equipment,
(c) measures to contain accidental spillage in conformance with Subsection 4.3.7.,
(d) an overfill protection device in conformance with Sentence 4.3.1.8.(2), where a tight-filled connection is provided, and
(e) where the piping is connected to the storage tank at a point that is lower than the maximum fill level, an external valve to prevent gravity discharge in the event the piping is severed.
(5) In cases where a compartmentalized tank is used, the entire tank shall be treated as one tank with the aggregate of all compartments totalling the total capacity of that tank.
Containers
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.