fire code, O. Reg. 213/07
Section 4.5.9.7
Cite as fire code, O. Reg. 213/07, s. 4.5.9.7 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as permitted in Sentence (2), the transfer of flammable liquids or combustible liquids in a closed piping system by means of compressed air or other non-inert gas pressure shall not be permitted.
(2) A non-inert gas pressure is permitted to be used in a closed piping system referred to in Sentence (1) provided
(a) it is the vapour or gas of the flammable liquid or combustible liquid being transferred, or
(b) it is a vapour or gas that will not support combustion reaction and is non-reactive with the flammable liquid or combustible liquid being transferred.
Subsection 4.5.10. Operating Procedures for Piping Systems
Procedures
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.