fire code, O. Reg. 213/07
Section 4.5.9.1
Cite as fire code, O. Reg. 213/07, s. 4.5.9.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Pumps for flammable liquid or combustible liquid piping systems installed aboveground and outside of buildings shall be located not less than
(a) 3 m from the property line, and
(b) 1.5 m from building openings.
Pump houses and pump rooms
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.