The text

(1) Thermal electrical conduction heating conforming to Sentence (2) is permitted to be used by passing a low-voltage alternating current through the pipe. (2) Systems permitted in Sentence (1) shall be installed and tested as complete units and shall conform to the following: (a) unheated sections of piping shall be isolated from heated sections by means of nonconductive fittings, (b) thermostatic controls, high temperature limit controls and fuses shall have the lowest practical rating to ensure satisfactory operation, (c) all parts of the piping and fittings shall be enclosed by insulating coverings, and (d) switches, transformers, contactors and other spark-producing equipment shall be located in an area not subject to flammable vapours. (3) Upon completion of installation, systems permitted in Sentence (1) shall be tested to ensure that all components are functioning as intended. Open flames
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.