fire code, O. Reg. 213/07
Section 4.5.8.2
Cite as fire code, O. Reg. 213/07, s. 4.5.8.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Flammable liquid and combustible liquid piping is permitted to be heated by steam lines provided the minimum steam temperature and pressure to make the liquid fluid are used and Sentences (2) and (3) are complied with.
(2) A pressure regulator shall be provided in the steam line with a relief valve on the downstream side of the regulator.
(3) Piping and steam lines shall be enclosed in insulation conforming to the Building Code.
Electrical heating cables
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.