fire code, O. Reg. 213/07
Section 4.5.6.1
Cite as fire code, O. Reg. 213/07, s. 4.5.6.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except for vent risers and vertical fill piping systems, underground piping systems shall be of double-walled construction.
(2) Underground piping systems that are installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continue to meet those requirements are deemed to comply with Sentence (1) if the piping does not leak.
Location
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.