fire code, O. Reg. 213/07

Section 4.5.3.1

Cite as fire code, O. Reg. 213/07, s. 4.5.3.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Underground metallic piping systems in contact with the soil or groundwater shall be protected against corrosion in conformance with (a) CAN/ULC-S603.1, “Standard for External Corrosion Protection Systems for Steel Underground Tanks for Flammable and Combustible Liquids”, or (b) NACE SP0169, “Control of External Corrosion on Underground or Submerged Metallic Piping Systems”. (2) Except as provided in Sentence (1), all exposed or underground piping, valves, couplings, flanges and bolts that are fabricated of any ferrous substance shall be thoroughly coated with a rust-resistant compatible material. Subsection 4.5.4. Identification of Piping Systems Identification
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.