The text

(1) Materials for piping systems containing flammable liquids or combustible liquids shall be suitable for the maximum anticipated working pressures and operating temperatures and for the chemical properties of the contained liquid. (2) Except as provided in Sentence (3), the use of the following materials for piping systems referred to in Sentence (1) shall not be permitted: (a) materials that are subject to failure from internal stress or rupture by mechanical damage, or (b) combustible or low-melting-point materials that are subject to failure in fires. (3) Metallic and non-metallic piping systems are permitted to be used for underground installations, provided they conform to CAN/ULC-S679, “Standard for Metallic and Nonmetallic Underground Piping for Flammable and Combustible Liquids”. (4) Except as provided in Sentence (5), where steel piping is used, it shall conform to (a) API SPEC 5L, “Line Pipe”, (b) ASTM A53/A53M, “Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless”, or (c) CSA Z245.1, “Steel Pipe”. (5) Where service pressures exceeding 875 kPa (gauge) may occur, piping and fittings shall be designed in conformance with ASME B31.3, “Process Piping”. (6) Underground piping systems shall include piping in tank sumps, transition sumps and dispenser sumps. Special materials
Read the fire code on e-Laws ↗