(1) Except as provided in Sentence (6), maintenance shall not be carried out on piping systems while they are under pressure.
(2) If connections or piping are to be opened, the system shall be drained of flammable liquids and combustible liquids.
(3) Where equipment for handling flammable liquids or combustible liquids has to be repaired, it shall be removed and taken to maintenance areas when possible.
(4) Tags shall be attached to all valves on piping systems that are shut off for maintenance purposes to indicate that such valves are not to be opened.
(5) Piping that has been used for the transfer of flammable liquids or combustible liquids shall be removed or capped when it is no longer intended to be used.
(6) The maintenance of pressurized piping systems shall be carried out in conformance with
(a) API STD 1104, “Welding of Pipelines and Related Facilities”,
(b) API RP 2200, “Repairing Crude Oil, Liquefied Petroleum Gas, and Product Pipelines”, or
(c) API RP 2201, “Safe Hot Tapping Practices in the Petroleum and Petrochemical Industries”.