fire code, O. Reg. 213/07
Section 4.5.10.5
Cite as fire code, O. Reg. 213/07, s. 4.5.10.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) A visual inspection routine for the prompt detection of obviously abnormal conditions shall be established and shall be performed at least once each shift.
(2) A visual inspection shall be made at least once during each day of operation of all aboveground piping systems, pumps and other ancillary equipment to detect leakage, and any leakage shall be repaired as quickly as practicable.
(3) Where necessary, flammable vapour indicators shall be used to detect leakage.
(4) Open flames and spark-producing devices shall not be used for leakage detection referred to in Sentence (2).
Operational tests
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.