fire code, O. Reg. 213/07
Section 4.4.1.3
Cite as fire code, O. Reg. 213/07, s. 4.4.1.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentence (2), when a leak detection test required by this Section detects a leak in a storage tank, piping system or sump, the leaking components or system shall be
(a) repaired and tested,
(b) replaced, or
(c) removed.
(2) When a leak detection test required by this Section detects a leak in a single-walled construction underground storage tank or piping system, the leaking components or system shall be
(a) replaced in conformance with Articles 4.3.8.1. and 4.5.6.1., or
(b) taken out of service in conformance with Subsection 4.3.16.
(3) Where a leak is detected as described in Sentence (1) or (2), the escaped liquid shall be removed in conformance with Subsection 4.1.6.
(4) The Chief Fire Official shall be notified within 24 h of detection of a leak referred to in Sentence (1).