fire code, O. Reg. 213/07
Section 4.3.8.6
Cite as fire code, O. Reg. 213/07, s. 4.3.8.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Underground steel storage tanks shall be installed in conformance with Appendix A of CAN/ULC-S603.1, “Standard for External Corrosion Protection Systems for Steel Underground Tanks for Flammable and Combustible Liquids”.
(2) Underground reinforced plastic storage tanks shall be installed in conformance with Appendix B of CAN/ULC-S615, “Standard for Fibre Reinforced Plastic Underground Tanks for Flammable and Combustible Liquids”.
(3) Underground storage tanks shall not be placed in direct contact with concrete slabs but shall be separated by not less than 150 mm of sand or other suitable reinforced material to evenly distribute the weight of the tank on the supporting base.
Filling
Read the fire code on e-Laws ↗