The text

(1) Liquids, debris and precipitation shall not accumulate in the contained space created by the secondary containment. (2) Provisions shall be made for removing liquid from the secondary containment in conformance with Subsection 4.1.6. (3) Controls for the liquid removal system required in Sentence (2) shall be (a) normally closed, (b) accessible under fire exposure conditions, and (c) located so they can be operated from outside the contained space. Use of secondary containment