fire code, O. Reg. 213/07

Section 4.3.6.4

Cite as fire code, O. Reg. 213/07, s. 4.3.6.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentence (3), connections used as part of normal operating conditions for filling or emptying storage tanks for flammable liquids and combustible liquids shall be located (a) outside buildings, (b) at a location free of sources of ignition, and (c) not less than 1.5 m away from building openings. (2) Connections for filling or emptying storage tanks shall be kept closed to prevent leakage when not in use. (3) A filling connection described in Sentence (1) is permitted to be located inside a building if (a) this is made necessary (i) by a process or activity located indoors and to which the tank is directly associated, or (ii) for the collection of used liquids, and (b) the fill piping is provided with means to prevent flammable vapours from returning to the building. (4) Connections for filling or emptying storage tanks shall be provided with a spill containment device designed to catch, retain and provide for the evacuation of spilled flammable liquids or combustible liquids in conformance with CAN/ULC-S663, “Standard for Spill Containment Devices for Flammable and Combustible Liquid Aboveground Storage Tanks”. Subsection 4.3.7. Secondary Containment for Aboveground Storage Tanks General