fire code, O. Reg. 213/07
Section 4.3.5.2
Cite as fire code, O. Reg. 213/07, s. 4.3.5.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Normal vent pipe outlets for storage tanks of Class I liquids
(a) shall be located outside buildings not less than
(i) 3.5 m above the adjacent ground level, and
(ii) 1.5 m from any building opening, and
(b) shall discharge so that flammable vapours will not enter the building or be trapped near any part of the building.
(2) Normal vent pipe outlets for storage tanks of Class II or IIIA liquids shall discharge outside buildings not less than
(a) 2 m above the adjacent ground level, and
(b) 1.5 m from any building opening.
(3) Emergency vent outlets for storage tanks shall discharge outside buildings not less than 1.5 m from any building opening and from any combustible component of any building’s exterior wall.
Interconnection of vent piping
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.