fire code, O. Reg. 213/07
Section 4.3.16.4
Cite as fire code, O. Reg. 213/07, s. 4.3.16.4 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) When an aboveground storage tank will be out of service or unsupervised for a period not exceeding 180 days, the piping from the tank shall be capped or the valves that are necessary to achieve similar isolation of the tank shall be closed and securely locked.
(2) Where a storage tank referred to in Sentence (1) contains flammable liquids or combustible liquids, the liquid level in the tank shall be measured and compared with subsequent readings taken at intervals not greater than one month.
(3) When an aboveground storage tank will be out of service or unsupervised for a period exceeding 180 days
(a) all liquid and vapours shall be removed from the storage tank and its connected piping, and
(b) the storage tank markings shall clearly indicate that the tank is empty.