fire code, O. Reg. 213/07

Section 4.3.14.1

Cite as fire code, O. Reg. 213/07, s. 4.3.14.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Rooms for storage tanks inside buildings, referred to in Sentence 4.3.13.4.(1), shall be (a) separated from the rest of the building by a fire separation having a fire-resistance rating of at least 2 h, (b) designed to contain a spill equal to at least 100% of the volume of the largest storage tank or to drain away spilled flammable liquids or combustible liquids, (c) made liquid-tight where the walls join the floor, (d) used for no other purposes than the storage and handling of flammable liquids or combustible liquids, and (e) provided with natural or mechanical ventilation in conformance with Subsection 4.1.7. Clearances