fire code, O. Reg. 213/07

Section 4.3.12.3

Cite as fire code, O. Reg. 213/07, s. 4.3.12.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Fill piping and discharge piping shall enter underground storage tanks only through the top of the tank and discharge piping used in suction systems shall be sloped toward the storage tanks. (2) The fill point of an underground storage tank shall not be located higher than the discharge point of the tank’s vent. (3) Except as provided in Sentence (5), connections used as part of normal operating conditions for filling or emptying storage tanks for flammable liquids and combustible liquids shall be located (a) outside buildings, (b) at a location free of sources of ignition, and (c) not less than 1.5 m away from building openings. (4) Connections for filling or emptying storage tanks described in Sentence (3) shall be kept closed to prevent leakage when not in use. (5) A filling connection described in Sentence (3) is permitted to be located inside a building if (a) this is made necessary (i) by a process or activity located indoors and to which the storage tank is directly associated, or (ii) for the collection of used liquids, and (b) the fill piping is provided with means to prevent flammable vapours from returning to the building. (6) If a fill piping system has an offset component from the fill point on the storage tank, all fill pipes shall be (a) double-walled, (b) sloped to the storage tank, and (c) electronically monitored for leak detection in conformance with Section 4.4. (7) Where the fill point is below the normal liquid level in the storage tank (a) the fill line shall be equipped with a manual or automatic valve located at the fill point to prevent spillage when the fill cap is removed, and (b) if the storage tank contains flammable liquids or combustible liquids, the fill line drop tube shall be equipped with a method to prevent siphoning of the tank's content should a leak occur in the fill line. (8) Fill piping systems that are installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continue to meet those requirements are deemed to comply with Sentences (6) and (7). Subsection 4.3.13. Installation of Storage Tanks inside Buildings Occupancy
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.