fire code, O. Reg. 213/07

Section 4.3.11.3

Cite as fire code, O. Reg. 213/07, s. 4.3.11.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Vent pipe outlets from underground storage tanks for Class I liquids (a) shall be located outside buildings higher than the fill pipe openings but not less than (i) 3.5 m above the adjacent ground level, (ii) 1.5 m from any building opening, and (iii) 7.5 m from any dispenser, and (b) shall discharge so that flammable vapours will not enter building openings or be trapped near any part of the building. (2) Vent pipe outlets from underground storage tanks for Class II or IIIA liquids shall be located outside buildings at a height that is above the fill pipe opening but not less than 2 m above finished ground level. (3) Vent pipes from underground storage tanks for flammable liquids or combustible liquids shall not be obstructed by any device that may cause excessive back pressure, except that vent pipes from underground storage tanks for Class II or IIIA liquids are permitted to be fitted with return bends, coarse screens or other devices to minimize the entry of foreign material. (4) Vent piping shall enter the storage tank through the top of the tank and shall not extend into the tank more than 25 mm. (5) Vent piping shall be (a) installed so that any nominally horizontal run shall slope towards the storage tank, (b) constructed without traps, (c) adequately supported to prevent sagging, and (d) where necessary, protected against mechanical damage. (6) Vent piping shall be tested for leaks at the commissioning stage in conformance with Clause 4.4.1.2.(1)(a). (7) Vent piping with operational vent alarms that are installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continue to meet those requirements are deemed to comply with Sentence (4). Interconnection of vent pipes
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.