fire code, O. Reg. 213/07

Section 4.3.1.8

Cite as fire code, O. Reg. 213/07, s. 4.3.1.8 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as required in Sentences (2) and (3), a storage tank shall be prevented from being overfilled by providing (a) continuous supervision of the filling operations by persons qualified to supervise such operations, or (b) an overfill protection device conforming to CAN/ULC-S661, “Standard for Overfill Protection Devices for Flammable and Combustible Liquid Storage Tanks”. (2) Except as provided in Sentence (3), tight-filled aboveground horizontal storage tanks and underground storage tanks shall be prevented from being overfilled by providing a positive shut-off device conforming to CAN/ULC-S661, “Standard for Overfill Protection Devices for Flammable and Combustible Liquid Storage Tanks”. (3) Storage tanks that are filled remotely with used lubricating oil described in Article 4.1.2.4. shall be prevented from being overfilled by providing an overfill protection device in accordance with Clause (1)(b). (4) Storage tanks that are installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continue to meet those requirements are deemed to comply with Sentences (1), (2) and (3). Installation and use