fire code, O. Reg. 213/07

Section 4.3.1.2

Cite as fire code, O. Reg. 213/07, s. 4.3.1.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as permitted in Sentences (3) and (5) and in Section 4.10., atmospheric storage tanks shall be built in conformance with the following: (a) except as provided in Sentence (2), API SPEC 12B, “Specification for Bolted Tanks for Storage of Production Liquids”, (b) except as provided in Sentence (2), API SPEC 12D, “Specification for Field Welded Tanks for Storage of Production Liquids”, (c) except as provided in Sentence (2), API SPEC 12F, “Specification for Shop Welded Tanks for Storage of Production Liquids”, (d) API STD 650, “Welded Tanks for Oil Storage”, (e) CAN/ULC-S601, “Standard for Shop Fabricated Steel Aboveground Tanks for Flammable and Combustible Liquids”, (f) CAN/ULC-S602, “Standard for Steel Aboveground Tanks for Fuel Oil and Lubricating Oil”, (g) CAN/ULC-S603, “Standard for Steel Underground Tanks for Flammable and Combustible Liquids”, (h) CAN/ULC-S603.1, “Standard for External Corrosion Protection Systems for Steel Underground Tanks for Flammable and Combustible Liquids”, (i) CAN/ULC-S615, “Standard for Fibre Reinforced Plastic Underground Tanks for Flammable and Combustible Liquids”, (j) CAN/ULC-S652, “Standard for Tank Assemblies for the Collection, Storage and Removal of Used Oil”, (k) CAN/ULC-S653, “Aboveground Steel Contained Tank Assemblies for Flammable and Combustible Liquids”, (l) ULC-S655, “Aboveground Protected Tank Assemblies for Flammable and Combustible Liquids”, (m) CAN/ULC-S677, “Standard for Fire Tested Aboveground Tank Assemblies for Flammable and Combustible Liquids”, or (n) ANSI/CAN/UL/ULC 2258, “Standard for Aboveground Nonmetallic Tanks for Fuel Oil and Other Combustible Liquids”. (2) Tanks built in conformance with Clause (1)(a), (b) or (c) shall be (a) used only for the storage of crude petroleum and oil field production liquids, and (b) provided with emergency venting that (i) conforms to API STD 2000, “Venting Atmospheric and Low-Pressure Storage Tanks”, and (ii) is compatible with the design features of the tank. (3) When necessitated by possible contamination of the liquid to be stored or possible rapid corrosion of the tank, storage tanks need not conform to Sentence (1), provided that they are designed and built in conformance with good engineering practice for the material being used. (4) Atmospheric storage tanks shall not be used for the storage of flammable liquids or combustible liquids at temperatures at or above their boiling points. (5) Atmospheric storage tanks that are installed and currently in use, that met the requirements of this Code on December 31, 2025, as it read at the time, and that continue to meet those requirements are deemed to comply with Sentence (1). Low pressure storage tanks and pressure vessels
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.