fire code, O. Reg. 213/07

Section 4.2.8.2

Cite as fire code, O. Reg. 213/07, s. 4.2.8.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentences (2) and (3) and in Article 4.2.8.4., the quantity of flammable liquids and combustible liquids permitted to be located outside of storage rooms conforming to Subsection 4.2.7., 4.2.9. or 4.3.14., or storage cabinets conforming to Subsection 4.2.10., in any one fire compartment of a building, shall not be more than (a) 600 L of flammable liquids and combustible liquids in closed containers, of which not more than 100 L shall be Class IA liquids, and (b) 5000 L of Class IB, IC, II and IIIA liquids in storage tanks or portable tanks. (2) Where required for normal plant activity, quantities of flammable liquids and combustible liquids are permitted to exceed those specified in Sentence (1), but shall not be greater than the supply for one day of normal operation. (3) Where larger quantities than those permitted by Sentence (2) are required, such quantities shall be in storage tanks installed in conformance with Sentence 4.3.13.4.(2). Handling
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.