fire code, O. Reg. 213/07
Section 4.2.7.5
Cite as fire code, O. Reg. 213/07, s. 4.2.7.5 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentences (2) and (3), the storage of flammable liquids and combustible liquids in storage areas specified in Clause 4.2.7.2.(1)(a) shall
(a) conform to Table 4.2.7.5.A.
(i) where it consists of palletized or solid piled storage, or
(ii) where stored in racks in buildings not protected in conformance with Article 4.2.7.6., or
(b) conform to Table 4.2.7.5.B. where stored in racks in buildings protected in conformance with Article 4.2.7.7.
(2) Where a building or part of building is designed for the storage of flammable liquids or combustible liquids, there is no limit on the total quantity of storage per fire compartment provided the building or part of building is separated from adjacent buildings or parts of buildings by
(a) a firewall having a fire-resistance rating of at least 4 h, or
(b) spatial separation in conformance with the Building Code.
(3) The quantities in each individual storage area shall not exceed the quantities specified in
(a) Table 4.2.7.5.A. for palletized or solid pile storage or unprotected rack storage, or
(b) Table 4.2.7.5.B. for protected rack storage.
(4) Where containers for two or more liquids having different flash points are stored together in a single individual storage area, the maximum quantity permitted in the individual storage area shall equal that permitted for the liquid with the lowest flash point.
(5) When flammable liquids or combustible liquids are stored in solid pile or rack storage configurations or a combination of both in a single fire compartment, the maximum quantity permitted for each class of liquid shall be calculated as follows:
(qIA/QIA + qIB/QIB + qIC/QIC + qII/QII + qIIIA/QIIIA)Rack +
(qIA/QIA + qIB/QIB + qIC/QIC + qII/QII + qIIIA/QIIIA)Solid Pile ≤ 1
where
qIA, IB or IC = actual quantity of Class IA, IB or IC liquids present in a rack or solid pile, in litres,
qII = actual quantity of Class II liquids present in a rack or solid pile, in litres,
qIIIA = actual quantity of Class IIIA liquids present in a rack or solid pile, in litres,
QIA, IB, IC = maximum quantity of Class IA, IB or IC liquids permitted in Table 4.2.7.5.A. or Table 4.2.7.5.B. for the arrangement, in litres,
QII = maximum quantity of Class II liquids permitted in Table 4.2.7.5.A. or Table 4.2.7.5.B. for the arrangement, in litres, and
QIIIA = maximum quantity of Class IIIA liquids permitted in Table 4.2.7.5.A. or Table 4.2.7.5.B. for the arrangement, in litres.
Table 4.2.7.5.A.
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.