fire code, O. Reg. 213/07

Section 4.2.6.3

Cite as fire code, O. Reg. 213/07, s. 4.2.6.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Except as provided in Sentence (2), the storage of flammable liquids and combustible liquids outside of a cabinet or storage room required in Article 4.2.6.2. is permitted, provided such storage does not exceed (a) 10 L, including not more than 5 L of Class I liquids, in a single room, or (b) 250 L, including not more than 60 L of Class II liquids or 10 L of Class I liquids, in a single fire compartment with a fire-resistance rating of at least 45 min. (2) In the automotive shops or industrial arts area of an educational facility, storage of up to 75 L of flammable liquids and combustible liquids, including not more than 25 L of Class I liquids, shall be permitted outside of a cabinet or storage room as required in Article 4.2.6.2. Containers
Read the fire code on e-Laws ↗