fire code, O. Reg. 213/07
Section 4.2.4.2
Cite as fire code, O. Reg. 213/07, s. 4.2.4.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentence (4) and in Articles 4.2.4.5. and 4.2.4.6., the maximum quantity of flammable liquids or combustible liquids stored in a building or in a fire compartment with a fire-resistance rating of at least 1 h shall conform to Sentences (2) and (3).
(2) When a single class of flammable liquid or combustible liquid is stored in a building or in a fire compartment with a fire-resistance rating of at least 1 h, the total quantity of liquid shall not exceed
(a) 30 L of Class I liquids,
(b) 150 L of Class II liquids, or
(c) 600 L of Class IIIA liquids.
(3) When two or more classes of flammable liquid or combustible liquid are stored in the same building or in a fire compartment having a fire-resistance rating not less than 1 h, the total quantity permitted for each class of liquid shall be calculated as follows:
qI/30 + qII/150 + qIIIA/600 ≤ 1
where
qI = actual quantity of Class I liquids present, in litres,
qII = actual quantity of Class II liquids present, in litres, and
qIIIA = actual quantity of Class IIIA liquids present, in litres.
(4) Quantities of flammable liquids or combustible liquids exceeding those permitted in Sentence (1) are permitted, provided they are kept
(a) in storage cabinets conforming to Subsection 4.2.10., except that the total quantity of flammable liquids and combustible liquids stored in such cabinets shall not exceed the quantity permitted for one cabinet, or
(b) in a storage room conforming to Subsection 4.2.9. and having no openings that communicate directly with the public portions of the building.
Storage cabinets and storage rooms
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.