fire code, O. Reg. 213/07
Section 4.2.11.1
Cite as fire code, O. Reg. 213/07, s. 4.2.11.1 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Except as provided in Sentence (2), the quantities and clearances for flammable liquids and combustible liquids stored in containers in outdoor storage areas shall conform to Table 4.2.11.1.
(2) The clearances required in Sentence (1) do not apply where not more than 5000 L of flammable liquids or combustible liquids are stored adjacent to a building on the same property, provided that either
(a) the building is limited to 1 storey in building height and is used primarily for the storage or handling of flammable liquids or combustible liquids, or
(b) the exposed wall has a fire-resistance rating of at least 2 h and has no openings within 3 m of such outdoor storage.
Table 4.2.11.1.
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.