(1) Except as permitted in Sentence (2), in maturing warehouses, at least one portable extinguisher having a rating of 4-A:30-B:C shall be located adjacent to each exit.
(2) Hose stations in conformance with Article 6.2.6.6. are permitted to be installed in lieu of portable extinguishers at locations required in Sentence (1), and spaced so that the travel distance to the nearest hose is not greater than 25 m.
(3) At least one portable extinguisher having a rating of 30-B:C shall be located on each industrial lift truck.
(4) In addition to the requirements set out in Sentences (1) to (3), portable extinguishers shall be provided in conformance with Section 6.2.