fire code, O. Reg. 213/07

Section 4.1.8.2

Cite as fire code, O. Reg. 213/07, s. 4.1.8.2 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) When Class I liquids are dispensed from or into a container or a storage tank (a) all metallic or electrically conducting material in the transfer system shall be electrically bonded and grounded, or (b) if the container or tank is made of non-electrically conducting material, measures shall be taken to minimize the potential for static electric charge to develop. (2) Except as provided in Sentence (3), when Class I liquids are transferred into a storage tank through the top of the tank, the fill pipe shall terminate within 150 mm of the bottom of the tank. (3) Sentence (2) shall not apply when (a) the storage tank vapour space cannot exceed 25% of the lower explosive limit or is filled with an inert gas that prevents the ignition of the vapour mixture, or (b) the liquid being transferred has a minimum conductivity that prevents the accumulation of static electricity. (4) Fill pipes referred to in Sentence (2) shall be installed in such a way as to minimize vibration of the pipe. Transfer
Read the fire code on e-Laws ↗