fire code, O. Reg. 213/07

Section 4.1.7.6

Cite as fire code, O. Reg. 213/07, s. 4.1.7.6 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026

The text

(1) Where a mechanical ventilation system is installed in conformance with Article 4.1.7.2., and where exhaust air is recirculated, a fail-safe vapour detection and alarm system shall be provided (a) to continuously monitor the flammable vapour concentration in the exhaust air, and (b) if the vapour concentration in Clause (a) exceeds 25% of the lower explosive limit of the vapour, to (i) sound an alarm in an attended area, (ii) stop the recirculation of air, and (iii) redirect the exhaust air to an outdoor location. Exclusive use of ducts
Read the fire code on e-Laws ↗

Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.