fire code, O. Reg. 213/07
Section 4.1.6.3
Cite as fire code, O. Reg. 213/07, s. 4.1.6.3 · current to November 11, 2026 · consolidated from January 1, 2026 · read from e-Laws on November 16, 2026
The text
(1) Maintenance and operating procedures shall be established to prevent the escape of flammable liquids or combustible liquids to areas where they could create a fire or explosion hazard.
(2) Except as provided in Sentence (3), all reasonable steps shall be taken to recover escaped liquid and to remove or treat contaminated soil, surface water, ground water or aquatic sediments.
(3) Spilled or leaked flammable liquids or combustible liquids shall be
(a) flushed to a location where they will not create a fire or explosion hazard or any risk to public health or safety, or
(b) neutralized or absorbed and cleaned up with the aid of a product that is compatible and non-reactive with the liquid being cleaned up or a product that conforms to ULC/ORD-C410A, “Absorbents for Flammable and Combustible Liquids” and
(i) deposited in a receptacle conforming to Article 2.4.1.3., or
(ii) disposed of in a manner that does not create a fire or explosion hazard.
Spill procedure
Read the fire code on e-Laws ↗
Made under Fire Protection and Prevention Act, 1997, S.O. 1997, c. 4.